Understanding when a Fire Risk Appraisal of External Walls (FRAEW) is not required
October 2026
Understanding when a Fire Risk Appraisal of External Walls (FRAEW) is not required
October 2026
PAS 9980:2026 A More Logical and Proportionate Approach to External Wall Fire Risk Assessment
The publication of the revised PAS 9980 represents an important development in the assessment of fire risk associated with the external walls of existing blocks of flats.
In our opinion, this 2026 version provides greater clarity in several areas of the assessment process, supporting a more logical, consistent and proportionate approach to evaluating external wall fire risk. It also helps reduce overly conservative assessments by providing clearer guidance on the assessment process and the circumstances in which a FRAEW is unnecessary.
One particularly important improvement is the clearer identification of buildings and external wall constructions that should be considered inherently low risk, for which an FRAEW is not required.
This is significant because commissioning an FRAEW for every residential building without first considering whether one is necessary can result in unnecessary professional fees, delays and potentially disproportionate remedial works.
WHEN IS An FRAEW NOT REQUIRED?
The PAS 9980:2026 set out specific circumstances in which a building or its external wall construction should be deemed inherently low risk, such that an FRAEW is not required.
A. Buildings that are inherently low risk
Under Section 4.2, the following building types should be deemed inherently low risk:
Detached individual dwellinghouses;
Terraced or semi-detached dwellinghouses;
Blocks of flats having no more than two storeys above ground (i.e. ground floor and first floor only); and
Blocks of flats having no more than three storeys above ground (i.e. ground floor, first floor and second floor only) unless there is an obvious hazard associated with the external walls.
These provisions give flat owners and managing agents a clearer starting point when considering whether their building requires a specialist FRAEW.
FRAEW may not be required for block of flats with not more than 3 storeys, if no obvious hazard associated with external wall identified
B. External wall constructions that are inherently low risk
Section 4.3 identifies specific external wall constructions that should also be deemed inherently low risk, meaning an FRAEW is not required.
Solid masonry construction at least 150 mm thick where any insulation or other combustible materials are applied only as internal linings to rooms;
Walls formed of two leaves of masonry each at least 75 mm thick, with a cavity in between that might contain combustible materials, where the cavity is closed at its edges, including around openings;
External walls and attachments that are, save for some exceptions , entirely formed of materials that are of European classification A2-s1, d0 or A1 and where cavity barriers are provided either:
1) in line with compartment walls and floors; or
2) at the edges of all cavities, including around openings such as windows, doors and penetrations;
External wall construction without combustible attachments, closely matching that which has been successfully tested to BS 8414-1 or BS 8414-2, and classified to BR 135 [6] based on the test data.
External walls found with entirely non-combustible materails without cavity, An FRAEW would not be required.
WHY DOES THIS MATTER TO FLAT OWNERS AND MANAGING AGENTS?
In our experience, for some buildings, the relevant criteria are sufficiently straightforward that a flat owner, freeholder or managing agent would be able to establish whether the building falls within one of the specified categories, using reliable information about the building and its construction.
This can help stakeholders make better-informed decisions before committing to the cost of specialist assessments, and prevent unnecessary FRAEW.
Where the criteria are not clearly satisfied, the construction is uncertain, or an obvious hazard is present, the professional advice and investigation would also be minimized when there is sufficient evidence supporting that an FRAEW is not required.
The objective is not to avoid appropriate investigations. It is to ensure that investigations are undertaken where they are justified.
Disclaimer: This article is intended for general information only and does not constitute a fire risk assessment or professional advice for any particular building. The relevant provisions of PAS 9980 should be consulted in full. Whether a FRAEW is required depends on the applicable criteria and the specific circumstances of the building.